Publication:
Lightning impulse strength of 275 kV and 132 kV tower with composite crossarm

Date
2019
Authors
Abd Rahman M.S.
Ab Kadir M.Z.A.
Ab-Rahman M.S.
Osman M.
Nor S.F.M.
Journal Title
Journal ISSN
Volume Title
Publisher
Institute of Electrical and Electronics Engineers Inc.
Research Projects
Organizational Units
Journal Issue
Abstract
Severe lightning overvoltage is regarded to the multiple flashovers on the overhead lines. Therefore, it signifies the needs of having a robust insulation system, especially to those which highly susceptible to lightning strikes. In order to minimize the impact of lightning, it is necessary to evaluate lightning performance of the tower and its components before implementing any proposed design. Therefore, in this work, a feasibility study was done on proposed 275 kV and 132 kV transmission tower with composite crossarm installed. In order to assess the insulation strength of the tower against the lightning activities, lightning caused events i.e. backflashover and shielding failure were applied onto the tower models by using FEM based software. The CFO of the tower insulation were calculated based on the design provided, whereby it was complementary verified by the voltage and electric field profiles of the simulation. For each case, none had shown a voltage magnitude higher than the voltage supposed to possibly cause 50% chance of flashover. � 2019 IEEE.
Description
Electric insulation; Electric power transmission; Flashover; Towers; ANSYS Maxwell; Electric field profiles; Feasibility studies; Lightning activity; Lightning over-voltage; Lightning performance; Lightning strikes; Transmission tower; Lightning
Keywords
Citation
Collections