dc.description.abstractOn Load Tap Changer (OLTC) failure occurs is due to the insulation degradation and contacts failure inside it. Other than that, contacts wear influences the OLTC performances. The worn contacts will cause hotspots in the OLTC tank and cause the insulating oil to degrade faster. As a result, this will lead to the damage of complete transformer unit. Thus, the research work that has been carried out applied the Dissolved Gas Analysis (DGA) via latest Duval Triangle method during the diagnosis of OLTC at the first stage to provide early indication of OLTC's breakdown. The Static Winding Resistance Test is then applied at the second stage to figure out any increase of contact resistances for all phases. The capability of Static Winding Resistance Test in order to provide any sign of bad contacts in fixed condition can be done by comparing two different conditions which are before and after maintenance. � 2012 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo6230903
dc.identifier.doi10.1109/PEOCO.2012.6230903
dc.identifier.epage435
dc.identifier.scopus2-s2.0-84865018391
dc.identifier.spage432
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-84865018391&doi=10.1109%2fPEOCO.2012.6230903&partnerID=40&md5=2e2311490cf74275aee30a71f470da5a
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/30307
dc.pagecount3
dc.sourceScopus
dc.sourcetitle2012 IEEE International Power Engineering and Optimization Conference, PEOCO 2012 - Conference Proceedings
dc.subjectContact resistance
dc.subjectDissolved Gas Analysis (DGA)
dc.subjectDuval Triangle Method
dc.subjectOLTC
dc.subjectStatic Winding Resistance Test
dc.subjectContact resistance
dc.subjectDegradation
dc.subjectOptimization
dc.subjectBad contact
dc.subjectCondition assessments
dc.subjectDissolved gas analysis
dc.subjectDuval Triangle Method
dc.subjectHotspots
dc.subjectInsulation degradation
dc.subjectOLTC
dc.subjectOn-load tap changers
dc.subjectWinding resistances
dc.subjectEngineering research
dc.titleCondition assessment of OLTC using duval triangle and static winding resistance testen_US