Effect of earth grid conductor spacing on the safety criteria of substation earthing

dc.citedby4
dc.contributor.authorBuba S.D.en_US
dc.contributor.authorWan Ahmad W.F.en_US
dc.contributor.authorAb Kadir M.Z.A.en_US
dc.contributor.authorGomes C.en_US
dc.contributor.authorJasni J.en_US
dc.contributor.authorOsman M.en_US
dc.contributor.authorid55121228700en_US
dc.contributor.authorid57215968575en_US
dc.contributor.authorid25947297000en_US
dc.contributor.authorid57201335285en_US
dc.contributor.authorid25632671500en_US
dc.contributor.authorid7201930315en_US
dc.date.accessioned2023-05-16T02:46:00Z
dc.date.available2023-05-16T02:46:00Z
dc.date.issued2014
dc.description.abstractSite dependent parameters such as soil resistivity, maximum grid current, fault duration, shock duration, surface layer material resistivity, and grid geometry have substantial impact on the design and performance of an earth grid. The grid geometry, i.e. the area occupied by the grid system, conductor spacing and the depth of burial of earth grid specifically have much impact on the mesh, step, touch voltage and earth potential rise, while parameters such as the conductor diameter and the thickness of the surfacing material have less impact on the safety criteria. In this paper, a distribution substation earth grid was designed using the CDEGS software by varying the spacing between grid conductors (compression ratio) from 1 to 0.5 in steps of 0.1. The safety criteria were studied under three scenarios, without surface layer material, with surface layer material of resistivity 3000?-m, and surface layer material of resistivity 5000?-m. Results indicated that the grid resistance and earth potential rise were lower for a compression ratio 0.9, while the step and touch voltages were found to be similar for each case of surface layer material. © 2014 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo7062428
dc.identifier.doi10.1109/PECON.2014.7062428
dc.identifier.epage139
dc.identifier.scopus2-s2.0-84946690111
dc.identifier.spage134
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-84946690111&doi=10.1109%2fPECON.2014.7062428&partnerID=40&md5=1b7521acadfbc3710276cef48cba3fe8
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/21910
dc.publisherInstitute of Electrical and Electronics Engineers Inc.en_US
dc.relation.ispartofAll Open Access, Green
dc.sourceScopus
dc.sourcetitleConference Proceeding - 2014 IEEE International Conference on Power and Energy, PECon 2014
dc.titleEffect of earth grid conductor spacing on the safety criteria of substation earthingen_US