Publication:
Advancement of TDR technique for locating power cable insulation degradation

dc.citedby4
dc.contributor.authorKuan T.M.en_US
dc.contributor.authorAriffin A.M.en_US
dc.contributor.authorSedau M.M.B.en_US
dc.contributor.authorid49561583600en_US
dc.contributor.authorid16400722400en_US
dc.contributor.authorid57200282220en_US
dc.date.accessioned2023-05-29T06:39:56Z
dc.date.available2023-05-29T06:39:56Z
dc.date.issued2017
dc.description.abstractThis paper discusses the advancement of time domain reflectometry (TDR) technique for locating degradation in power cable insulation with and without jointing. TDR technique is commonly used for localizing processes in various fields. It applies the concept of radar where a signal propagates through a medium will be reflected when there is an impedance mismatch. However, the application of TDR technique in power cable is still limited and its potential to pinpoint the exact location of degradation in power cables is to be ascertained. This study conducts experiments to investigate the potential of this technique in pinpointing the location of degradation in power cable with and without jointing. Experiments are conducted on un-degraded cable without any joint and followed by cable with jointing up to 2 cable joints. For experiments with jointing, the un-degraded cable is sectionalized into 2 parts, and one of the sections is replaced by a degraded cable. Experiments are repeated by sectionalizing the un-degraded cable into 3 parts, and each section is replaced with a degraded cable up to 2 sections. TDR results from all experiments are compiled and then analyzed. The results obtained from this study have proven that TDR technique is capable of identifying the degradation along a cable and at the same time pinpointing the exact location of degraded cable section.en_US
dc.description.natureFinalen_US
dc.identifier.doi10.18517/ijaseit.7.6.2315
dc.identifier.epage1982
dc.identifier.issue6
dc.identifier.scopus2-s2.0-85040579686
dc.identifier.spage1976
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85040579686&doi=10.18517%2fijaseit.7.6.2315&partnerID=40&md5=715893bd73e3185e20aaff5724412b6e
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/23379
dc.identifier.volume7
dc.publisherInsight Societyen_US
dc.relation.ispartofAll Open Access, Hybrid Gold
dc.sourceScopus
dc.sourcetitleInternational Journal on Advanced Science, Engineering and Information Technology
dc.titleAdvancement of TDR technique for locating power cable insulation degradationen_US
dc.typeArticleen_US
dspace.entity.typePublication