Publication:
Sectionalization of degraded polymeric cable with multiple joints using TDR technique

dc.contributor.authorKuan T.M.en_US
dc.contributor.authorAriffin A.M.en_US
dc.contributor.authorRaymond W.J.K.en_US
dc.contributor.authorid49561583600en_US
dc.contributor.authorid16400722400en_US
dc.contributor.authorid55193255600en_US
dc.date.accessioned2023-05-29T08:06:41Z
dc.date.available2023-05-29T08:06:41Z
dc.date.issued2020
dc.descriptionMATLAB; Polymers; Time domain analysis; Cable replacement; Fault localization; Insulated cables; Multiple joints; Polymeric cables; TDR techniques; Time-domain reflectometry techniques; XLPE cables; Cablesen_US
dc.description.abstractThis paper presents the study on time domain reflectometry (TDR) technique in sectionalizing degraded cable along a polymeric insulated cable with multiple joints. TDR has been widely used for fault localization in polymeric cables. However, it only gives an average condition of the cable and could not pinpoint the degraded section along a cable especially for cable with jointing. Hence, this paper investigates the ability of TDR technique to pinpoint degraded cable section for an XLPE cable with two joints. The TDR system is modelled in MATLAB with a 300-metre XLPE cable that is divided into three equal lengths of 100 m and joint together using two cable joints. The location of degraded cable section is varied to study the ability of TDR in detecting degraded cable at various locations. Simulation results are then validated experimentally with the same cable configurations. Findings from validation of results show that TDR is capable of pinpointing the degraded cable section which allow sectionalization to take place for cable replacement. � 2020 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo9314302
dc.identifier.doi10.1109/PECon48942.2020.9314302
dc.identifier.epage250
dc.identifier.scopus2-s2.0-85100561248
dc.identifier.spage245
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85100561248&doi=10.1109%2fPECon48942.2020.9314302&partnerID=40&md5=1dfbbf91eb0595dcc388c708a347a132
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/25079
dc.publisherInstitute of Electrical and Electronics Engineers Inc.en_US
dc.sourceScopus
dc.sourcetitlePECon 2020 - 2020 IEEE International Conference on Power and Energy
dc.titleSectionalization of degraded polymeric cable with multiple joints using TDR techniqueen_US