Publication:
Analysis of a geomagnetic induced current on a three-phase power transformer and power system

dc.citedby1
dc.contributor.authorZawawi A.A.en_US
dc.contributor.authorAziz N.F.A.en_US
dc.contributor.authorKadir M.Z.A.A.en_US
dc.contributor.authorHashim H.en_US
dc.contributor.authorid57219849903en_US
dc.contributor.authorid57221906825en_US
dc.contributor.authorid25947297000en_US
dc.contributor.authorid56644250200en_US
dc.date.accessioned2023-05-29T09:09:03Z
dc.date.available2023-05-29T09:09:03Z
dc.date.issued2021
dc.descriptionElectric grounding; Electric power utilization; Geomagnetism; Induced currents; Intercalation; Power transformers; Reactive power; Software testing; System stability; Current flows; Geomagnetic induced currents; Ground-based network; High impact events; Space weather; Steady-state condition; Three phase power transformers; Transmission systems; Electric power transmissionen_US
dc.description.abstractA geomagnetic induced current (GIC), resulting from adverse space weather, has a low occurrence rate but the potential for high impact events. Such events can disrupt the operation of a power system, especially the power transformer as the current flows in the transmission lines and through the transformer ground points. It is a well-documented fact that a GIC can cause a significant threat to ground-based networks as the induced current can enter into the transmission system through the wye-grounded transformers. This paper presents a simulation of a GIC on an IEEE 9-bus test system under steady-state conditions using PSCAD/EMTDC software. The main focus of this paper is the effects of a GIC on a three-phase power transformer that includes half cycle saturation and reactive power consumption. Based on the simulation results under GIC conditions, the magnitude flux and magnetising current of the power transformer as well as reactive power consumption increase and may lead to power system instability. � 2021 Published under licence by IOP Publishing Ltd.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo12008
dc.identifier.doi10.1088/1742-6596/1768/1/012008
dc.identifier.issue1
dc.identifier.scopus2-s2.0-85102416213
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85102416213&doi=10.1088%2f1742-6596%2f1768%2f1%2f012008&partnerID=40&md5=eec2e2b8f88811307fd69d477799c77c
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/26321
dc.identifier.volume1768
dc.publisherIOP Publishing Ltden_US
dc.relation.ispartofAll Open Access, Gold
dc.sourceScopus
dc.sourcetitleJournal of Physics: Conference Series
dc.titleAnalysis of a geomagnetic induced current on a three-phase power transformer and power systemen_US
dc.typeConference Paperen_US
dspace.entity.typePublication
Files
Collections