Publication:
Modelling and Analysis of 18-Pulse Rectification System for DC Traction Power Substation

dc.contributor.authorShukran A.I.M.en_US
dc.contributor.authorToh C.L.en_US
dc.contributor.authorTan C.W.en_US
dc.contributor.authorid57429421900en_US
dc.contributor.authorid8690228000en_US
dc.contributor.authorid35216732200en_US
dc.date.accessioned2023-05-29T09:10:08Z
dc.date.available2023-05-29T09:10:08Z
dc.date.issued2021
dc.descriptionDC transformers; Electric rectifiers; Electric substations; IEEE Standards; Reactive power; Rectifying circuits; 18-pulse rectification; Ac and dc; AC filters; Eighteen-pulse diode rectifier; Grid current; Harmonics distortion; Modelling and analysis; Phaseshifting transformer (PST); Pulse diode rectifiers; Traction power sub stations; Harmonic analysisen_US
dc.description.abstractEighteen-pulse rectifier had been proposed to replace the conventional twelve-pulse rectifier as it may further minimize the ac and dc harmonics distortions. This paper presents a simulation study of implementing an eighteen-pulse rectification system for future dc traction power substation. A phase-shifting transformer with angle displacement of 0,-20, and +20 degrees and three unit of six-pulse diode rectifier are modelled and validated via simulation. The preliminary results had confirmed that this 18-pulse rectification system managed to keep the utility grid voltage and current distortion indexes at about 2% without employing any harmonic filters. However, approximately 1 MVar reactive power must be compensated. Thus, passive harmonics filters are proposed. Three major power quality improvements are observed via simulation after implementing these filters. Firstly, the instantaneous reactive power is kept within the bands of � 0.12 MVar. Next, an approximate unity power factor can be seen from the grid system. Lastly, the grid voltage and current waveforms distortion are complied with IEEE standard for both normal and contingency operating condition. � 2021 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.doi10.1109/CENCON51869.2021.9627279
dc.identifier.epage179
dc.identifier.scopus2-s2.0-85123585808
dc.identifier.spage174
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85123585808&doi=10.1109%2fCENCON51869.2021.9627279&partnerID=40&md5=c06ad9e09c0e30abc0db59ca783c8982
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/26409
dc.publisherInstitute of Electrical and Electronics Engineers Inc.en_US
dc.sourceScopus
dc.sourcetitle5th IEEE Conference on Energy Conversion, CENCON 2021
dc.titleModelling and Analysis of 18-Pulse Rectification System for DC Traction Power Substationen_US
dc.typeConference Paperen_US
dspace.entity.typePublication