dc.description.abstractA low value of earth impedance may introduce sufficiently high fault current to activate the overcurrent protective device in order to clear the ground fault. Therefore, majority of the terrace houses projects use common ground slab steelwork as earth electrode to achieve low earth impedance. This earthing system is known as Foundation Grounding Scheme (FGS). However, a major safety concern about this earthing scheme is the AC touch voltage may exceed 50 V if one of the terrace houses is having fault occurrence. Hence, this paper aims to present a field measurement on the potential touch voltage for terrace houses using FGS technique under fault occurrence. The field test results confirmed that all houses which linked together are exposed to same level of potential touch voltage of about 186 V and the fault current is captured as 170 A before fault clearance at the house with fault. � 2023 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.doi10.1109/IEACon57683.2023.10370439
dc.identifier.epage109
dc.identifier.scopus2-s2.0-85182947015
dc.identifier.spage104
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85182947015&doi=10.1109%2fIEACon57683.2023.10370439&partnerID=40&md5=a8cefe29e94b7e4079929f4efc425cfb
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/34356
dc.pagecount5
dc.publisherInstitute of Electrical and Electronics Engineers Inc.en_US
dc.sourceScopus
dc.sourcetitleIEACon 2023 - 2023 IEEE Industrial Electronics and Applications Conference
dc.subjectearth loop impedance
dc.subjectearth resistance
dc.subjectequipotential bonding
dc.subjectfoundation grounding system
dc.subjectresidual current circuit breaker
dc.subjectElectric circuit breakers
dc.subjectElectric resistance
dc.subjectHouses
dc.subjectOvercurrent protection
dc.subjectTiming circuits
dc.subjectCircuit-breakers
dc.subjectCurrent circuits
dc.subjectEarth loop impedance
dc.subjectEarth loops
dc.subjectEarth resistance
dc.subjectEquipotential bonding
dc.subjectFoundation grounding system
dc.subjectGrounding systems
dc.subjectLoop impedance
dc.subjectResidual current
dc.subjectResidual current circuit breaker
dc.subjectElectric grounding
dc.titlePotential Safety Hazard in Terrace Houses with Foundation Grounding Schemeen_US
dc.typeConference Paperen_US
dspace.entity.typePublication
Files
Collections