Publication:
An experimental work on effect of bending down conductor with reinforced concrete

dc.contributor.authorAriffen A.M.en_US
dc.contributor.authorArshad S.N.M.en_US
dc.contributor.authorAb Kadir M.Z.A.en_US
dc.contributor.authorJasni J.en_US
dc.contributor.authorHalim N.H.en_US
dc.contributor.authorid55199804600en_US
dc.contributor.authorid56177750400en_US
dc.contributor.authorid25947297000en_US
dc.contributor.authorid25632671500en_US
dc.contributor.authorid57220194159en_US
dc.date.accessioned2023-05-29T08:11:34Z
dc.date.available2023-05-29T08:11:34Z
dc.date.issued2020
dc.descriptionElectric breakdown; Lightning protection; Walls (structural partitions); Air-termination systems; bent effect; Down-conductors; Impulse voltage; Lightning currents; Lightning protection systems; Reinforcement bar; Reliability and safeties; Reinforced concreteen_US
dc.description.abstractDown conductor is one of the pivotal parts of the Lightning Protection System (LPS) that diverting the lightning current captured by the air termination system to the earth termination system in each protected structure. A straight down conductor, is ideally suited for the best-case scenario regarding reliability and safety protection. One to aesthetical aspects, down conductor is undesirably bent in most current buildings. However, only the primary bare type of a down conductor is undergone such process, and bent at a certain degree which depending on the structure itself. Hence, this study is to investigate the bending degree effect on down conductors, by looking at breakdown voltage around the bent area with the presence of concrete wall and reinforcement bar. This experimental work conducted on a reduced scale of reinforced concrete which tested with high impulse voltage. It was determined that the bending down conductors has a significant effect on the bent (vertex) area with the interaction of concrete wall and reinforcement bar. � Published under licence by IOP Publishing Ltd.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo12036
dc.identifier.doi10.1088/1742-6596/1432/1/012036
dc.identifier.issue1
dc.identifier.scopus2-s2.0-85079097339
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85079097339&doi=10.1088%2f1742-6596%2f1432%2f1%2f012036&partnerID=40&md5=cfe3d695ec453a14c93fea3e7ad8887c
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/25603
dc.identifier.volume1432
dc.publisherInstitute of Physics Publishingen_US
dc.relation.ispartofAll Open Access, Bronze
dc.sourceScopus
dc.sourcetitleJournal of Physics: Conference Series
dc.titleAn experimental work on effect of bending down conductor with reinforced concreteen_US
dc.typeConference Paperen_US
dspace.entity.typePublication
Files
Collections