Publication:
Voltage sag acceptability assessment using multiple magnitude-duration function

dc.citedby37
dc.contributor.authorTan R.H.G.en_US
dc.contributor.authorRamachandaramurthy V.K.en_US
dc.contributor.authorid35325391900en_US
dc.contributor.authorid6602912020en_US
dc.date.accessioned2023-12-29T07:46:16Z
dc.date.available2023-12-29T07:46:16Z
dc.date.issued2012
dc.description.abstractA multiple magnitude-duration (MMD) function is proposed for voltage sag acceptability assessment. The MMD function is a statistical representation of voltage sag derived from its rms analysis. The MMD function maps a series of correlated sag magnitude and duration points onto the standard power acceptability curve, revealing the dynamic characteristic of voltage sag across the standard power acceptability curve. It allows nonrectangular voltage sag, such as voltage sag due to transformer energization, induction motor starting, multistage fault, self-extinguishing fault, and voltage sag influenced by induction load to be assessed. The practicality and advantage of the proposed MMD acceptability assessment is evaluated using practical data and IEEE1159.2 waveforms set on an ITIC and SEMI F47 standard power acceptability curve. The evaluation results show that the proposed MMD function yields higher resolution and improved acceptability assessment accuracy compared to the conventional single-point mapping assessment. � 1986-2012 IEEE.en_US
dc.description.natureFinalen_US
dc.identifier.ArtNo6261569
dc.identifier.doi10.1109/TPWRD.2012.2197423
dc.identifier.epage1990
dc.identifier.issue4
dc.identifier.scopus2-s2.0-84866735180
dc.identifier.spage1984
dc.identifier.urihttps://www.scopus.com/inward/record.uri?eid=2-s2.0-84866735180&doi=10.1109%2fTPWRD.2012.2197423&partnerID=40&md5=e55d2f160fd24c76d784d9a2c00ff46b
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/30283
dc.identifier.volume27
dc.pagecount6
dc.sourceScopus
dc.sourcetitleIEEE Transactions on Power Delivery
dc.subjectAcceptability assessment
dc.subjectpower acceptability curve
dc.subjectpower quality (PQ)
dc.subjectvoltage sag
dc.subjectInduction motors
dc.subjectAcceptability assessment
dc.subjectAssessment accuracy
dc.subjectDynamic characteristics
dc.subjectEvaluation results
dc.subjectFunction maps
dc.subjectHigher resolution
dc.subjectPower acceptability curves
dc.subjectRMS analysis
dc.subjectSelf-extinguishing
dc.subjectStatistical representations
dc.subjectTransformer energization
dc.subjectVoltage sags
dc.subjectWave forms
dc.subjectVoltage stabilizing circuits
dc.titleVoltage sag acceptability assessment using multiple magnitude-duration functionen_US