Publication:
Power Swing Blocker Algorithm for Distance Relay Design in Simulink Environment

dc.contributor.authorZairil Ashriq bin Mohd Zailanien_US
dc.date.accessioned2023-05-03T16:43:18Z
dc.date.available2023-05-03T16:43:18Z
dc.date.issued2020-09
dc.descriptionInterim Semester 2020/2021en_US
dc.description.abstractThis thesis reports about the development of a novel way in detecting the power swing. The purpose of this project was mainly to come up with an algorithm that could allow the distance mho relay to distinguish between power swing and three-phase fault in order to avoid any maltripping from happening. The power swing blocker algorithm was developed and tested by using Matlab SIMULINK. The algorithm was based on the ratio of second over first voltage harmonics that was constantly measured in the line and then been compared with a threshold value. The threshold value was obtained by running a few simulations before deciding on one absolute value that could produce consistent performance of the power swing blocker algorithm. The simulation carried out with the power swing blocker embedded in the distance mho relay had proven the reliability of this new approach in power swing detectionen_US
dc.identifier.urihttps://irepository.uniten.edu.my/handle/123456789/21375
dc.language.isoenen_US
dc.subjectPower Swing Blocker Algorithmen_US
dc.titlePower Swing Blocker Algorithm for Distance Relay Design in Simulink Environmenten_US
dspace.entity.typePublication
Files